<6. EXPLANATION OF BASIC ITEMS>

6-5

IM 01F06F00-01EN

Table 6.2

Available Units

Item

Block

Available Units

XD_
SCALE

AI1
(channel 1)

LIQUID:
Mass

GAS/STEAM:
Mass

kg/s (1322), kg/min (1323),
kg/h (1324), kg/d (1325),
t/s (1326), t/min (1327), t/h
(1328), t/d (1329), lb/s (1330),
lb/min (1331), lb/h (1332),
lb/d (1333)

LIQUID:
Volume

GAS/STEAM:
Volume

m

3

/s (1347), m

3

/min (1348),

m

3

/h (1349), m

3

/d (1350),

L/s (1351), L/min (1352),
L/h (1353), L/d (1354), CFS
[cf/s] (1356), CFM [cf/min]
(1357), CFH [cf/h] (1358),
ft3/d [cf/d] (1359), gal/s
[USgal/s] (1362), GPM
[USgal/min] (1363), gal/h
[USgal/h] (1364), gal/d
[USgal/d] (1365), ImpGal/s
[UKgal/s] (1367), ImpGal/min
[UKgal/min] (1368), ImpGal/h
[UKgal/h] (1369), ImpGal/d
[UKgal/d] (1370), bbl/s
(1371), bbl/min (1372), bbl/h
(1373), bbl/d (1374)

GAS
Std/Normal

N: Normal
S: Standard

SCFM [scf/min] (1360),
SCFH [scf/h] (1361), Nm

3

/s

(1522), Nm

3

/min (1523),

Nm

3

/h (1524), Nm

3

/d (1525)

Sm

3

/s (1527), Sm

3

/min

(1528), Sm

3

/h (1529), Sm

3

/d

(1530), NL/s (1532), NL/min
(1533), NL/h (1534), NL/d
(1535), SL/s (1537), SL/min
(1538), SL/h (1539), SL/d
(1540)

AI2
(channel 2)

Temperature °C (1001), °F (1002)

AI3
(channel 5)

m

3

/s (1347), m

3

/min (1348),

m

3

/h (1349), m

3

/d (1350),

L/s (1351), L/min (1352),
L/h (1353), L/d (1354), CFS
[cf/s] (1356), CFM [cf/min]
(1357), CFH [cf/h] (1358),
ft3/d [cf/d] (1359), gal/s
[USgal/s] (1362), GPM
[USgal/min] (1363), gal/h
[USgal/h] (1364), gal/d
[USgal/d] (1365), ImpGal/s
[UKgal/s] (1367), ImpGal/min
[UKgal/min] (1368), ImpGal/h
[UKgal/h] (1369), ImpGal/d
[UKgal/d] (1370), bbl/s
(1371), bbl/min (1372), bbl/h
(1373), bbl/d (1374)

Note: With the same setting, some units are represented

differently between the F

OUNDATION

Fieldbus

communication type and the HART or BRAIN
communication type of a digitalYEWFLO. Each unit
enclosed in brackets above shows the unit for the HART
or BRAIN communication type of a digitalYEWFLO,
corresponding to the preceding unit (for the F

OUNDATION

Fieldbus communication type).

Table 6.3

Setting Range of EU at 100 of XD_

SCALE Depending on Unit

Block

Unit Selected

Setting Range of EU at 100

AI1

Refer to Table 6.2

above 0.0

AI2

°C
°F

–273.15 to 999.9
–459.67 to 999.9

AI3

Refer to Table 6.2

above 0.0

OUT_SCALE:

Sets the range of output (from 0% to 100%).

Available units for OUT_SCALE are the same
as units for XD_SCALE in Table 6.2 and
percentage.

L_TYPE:

Specifi es the operation function of the AI1 block.

The factory default is “Direct”, so the input
delivered to CHANNEL is directly refl ected on
OUT. If set to “Indirect”, scaling by XD_SCALE
and OUT_SCALE is carried out and is refl ected
on OUT. “Indirect SQRT” is not used for a
digitalYEWFLO.

PV_FTIME:

Sets the time constant of the damping function

within AI block (primary delay) in seconds.

Alarm Priority:

Indicates the priority of the process alarm.

If a value of 3 or greater is set, an alarm is
transmitted. The factory default is 0. Four types
of alarm can be set: HI_PRI, HI_HI_PRI, LO_
PRI, and LO_LO_PRI.

Alarm Threshold:

Sets the threshold at which a process alarm is

generated. The factory default setting is a value
that does not generate an alarm. Four types of
alarm can be set: HI_LIM, HI_HI_LIM, LO_LIM,
and LO_LO_LIM.