2 function block execution control, Function block execution control -5 – Yokogawa digitalYEWFLO (DY-FF) User Manual

Page 22

Advertising
background image

<5. CONFIGURATION>

5-5

IM 01F06F00-01EN

Table 5.4

VCR Static Entry

Sub-

index

Parameter

Description

1

FasArTypeAndRole

Indicates the type and role of
communication (VCR). The
following 4 types are used for
the digitalYEWFLO.
0x32: Server (Responds to

requests from host.)

0x44: Source (Transmits

alarm or trend.)

0x66: Publisher (Sends AI,

DI block output to other
blocks.)

0x76: Subscriber (Receives

output of other blocks by
PID block.)

2

FasDllLocalAddr

Sets the local address
to specify a VCR in the
digitalYEWFLO. A range of 20
to F7 in hexadecimal.

3

FasDllConfi gured
RemoteAddr

Sets the node address of the
called party for communication
and the address (DLSAP or
DLCEP) used to specify VCR
in that address. For DLSAP
or DLCEP, a range of 20 to
F7 in hexadecimal is used.
Addresses in Subindex 2 and
3 need to be set to the same
contents of the VCR as the
called party (local and remote
are reversed).

4

FasDllSDAP

Specifi es the quality of
communication. Usually, one
of the following types is set.
0x2B: Server
0x01: Source (Alert)
0x03: Source (Trend)
0x91: Publisher/Subscriber

5

FasDllMaxConfi rm
DelayOnConnect

To establish connection for
communication, a maximum
wait time for the called party’s
response is set in ms. Typical
value is 60 seconds (60000).

6

FasDllMaxConfi rm
DelayOnData

For request of data, a

maximum wait time for the

called party’s response is

set in ms. Typical value is

60 secounds (60000).

7

FasDllMaxDlsduSize

Specifi es maximum DL
Service Data unit Size
(DLSDU). Set 256 for Server
and Trend VCR, and 64 for
other VCRs.

8

FasDllResidual
ActivitySupported

Specifi es whether connection
is monitored. Set TRUE (0xff)
for Server. This parameter
is not used for other
communication.

9

FasDllTimelinessClass Not used for the

digitalYEWFLO.

10

FasDllPublisherTime
WindowSize

Not used for the
digitalYEWFLO.

11

FasDllPublisher
SynchronizaingDlcep

Not used for the
digitalYEWFLO.

12

FasDllSubscriberTime
WindowSize

Not used for the
digitalYEWFLO.

13

FasDllSubscriber
SynchronizationDlcep

Not used for the
digitalYEWFLO.

Sub-

index

Parameter

Description

14

FmsVfdId

Sets VFD for the
digitalYEWFLO to be used.

0x1: System/network

management VFD

0x1234: Function block

VFD

15

FmsMaxOutstanding
ServiceCalling

Set 0 to Server. It is not used
for other applications.

16

FmsMaxOutstanding
ServiceCalled

Set 1 to Server. It is not used
for other applications.

17

FmsFeatures
Supported

Indicates the type of services
in the application layer. In
the digitalYEWFLO, it is
automatically set according to
specifi c applications.

These 33 VCRs are factory-set as shown in Table
5.5.

Table 5.5

VCR List

Index

(SM)

VCR

Number

Factory Setting

293

1

For system management (Fixed)

294

2

Server (LocalAddr = 0xF3)

295

3

Server (LocalAddr = 0xF4)

296

4

Server (LocalAddr = 0xF7)

297

5

Trend Source (LocalAddr = 0x07,
Remote Address=0x111)

298

6

Publisher (LocalAddr = 0x20)

299

7

Alert Source (LocalAddr = 0x07,
Remote Address=0x110)

300

8

Server (LocalAddr = 0xF9)

301 to 325

9 to 33

Not set

5.5.2 Function Block Execution Control

According to the instructions given in Section 5.3
“Function Block Link Defi nitions”, set the execution
cycle of the function blocks and schedule of
execution.

Advertising