<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF digitalYEWFLO>
A1-8
IM 01F06F00-01EN
Relative
Index
Index
Parameter Name
Factory Default
Write
Mode
Explanation
43 2043
LIMSW_2
_
HYSTERESIS
0
O/S
Sets the hysteresis of limit switch 2 to be applied
for resetting the LIMSW_2_VALUE_D to OFF after
LIMSW_2_TARGET went beyond LIMSW_2_SETPOINT
and LIMSW_2_VALUE_D turned ON (when used as a
high-limit switch), or after LIMSW_2_TARGET went below
LIMSW_2_SETPOINT and LIMSW_2_VALUE_D turned
ON (when used as a low-limit switch).
44
2044 LIMSW_2_UNIT
—
—
Indicates the unit set in LIMSW_2_TARGET.
45
2045 ALARM _PERFORM 0x1070
AUTO
A series of bits, each of which works as a switch to enable
and disable specifi c alarm(s); write zeros to the respective
bits in this parameter to disable desired alarms. (For
details, refer to APPENDIX 3 "OPERATION OF EACH
PARAMETER IN FAILURE MODE.")
46 2046
ARITHMETIC
_BLOCK
1 (Available)
—
Indicates whether the arithmetic block is available.
47
2047 SENSOR_STATUS
—
—
Indicates whether the fl ow detector has the built-in
temperature sensor:
1 = Standard
2 = Built-in Temp. Sensor
48 2048
THERMOMETER
_FUNCTION
1 (Monitor only)
(Note 5)
O/S
Selects the usage of the thermometer
function:
1 = Monitor only
2 = Saturated steam
3 = Superheat steam
4 = GAS: STD/Normal
5 = LIQUID: Mass
6 = Not use
(For details,
refer to
Section 6.2
"Transducer
Block
Parameters.")
49
2049 FLUID_TYPE
1 (LIQUID: Volume)
(Note 5)
O/S
Selects the type of the measured
process fl uid:
1 = LIQUID: Volume
2 = GAS/STEAM: Volume
3 = LIQUID: Mass
4 = GAS/STEAM: Mass
5 = GAS: STD/Normal
50 2050
TEMPERATURE
_UNIT
°C (1001) (Note 5)
O/S
Selects the unit of temperature.
51
2051 PROCESS_TEMP
15 (Note 5)
O/S
Sets the normal operating temperature of the process.
Setting range: –999.9 to 999.9
52
2052 BASE_TEMP
15 (Note 5)
O/S
Sets the temperature under the standard conditions of the
process. Setting range: from –999.9 to 999.9
53 2053
DENSITY_UNIT Kg/m
3
(1097) (Note 5) O/S
Selects the unit of density.
54 2054
PROCESS
_
DENSITY
1024 (Note 5)
O/S
Sets the density of the process fl uid under the normal
operating conditions. Setting range: 0.00001 to 32000
55
2055 BASE_DENSITY
1024 (Note 5)
O/S
Sets the density of the process fl uid under the standard
operating conditions. Setting range: 0.00001 to 32000
56
2056 PRESSURE_UNIT
MPaa (1545) (Note 5) O/S
Selects the unit of pressure between 1545 (= MPaa) and
1547 (= kPaa).
57 2057
PROCESS
_
PRESSURE
0.1013 (Note 5)
O/S
Sets the normal operating absolute pressure of the
process. Setting range: 0.00001 to 32000
58
2058 BASE _PRESSURE 0.1013 (Note 5)
O/S
Sets the absolute pressure under the standard conditions
of the process. Setting range: 0.00001 to 32000
59
2059 DEVIATION
1 (Note 5)
O/S
Sets the deviation factor of the process fl uid. Setting range:
0.001 to 10.0
60 2060
SECONDARY
_VALUE_FTIME
4 s
AUTO
Sets the time constant of damping for the temperature
calculation. Setting range: 0 to 99 s
61
2061 CABLE_LENGTH
0
O/S
Sets the length of cable between the fl ow detector and
remote amplifi er. Set 0 for an integral type digitalYEWFLO.
Setting range: 0 to 30 (meters)
62 2062
FIRST_TEMP
_COEF
0 O/S
Sets
the
fi rst temperature coeffi cient for the density
compensation of a liquid.
Setting range: –32000 to 32000
Unit: 1/TEMP_UNIT