<10. EXPLOSION PROTECTED TYPE INSTRUMENT>

10-5

IM 01F06F00-01EN

10.2 FM

Technical

Data

• Explosion Proof
Applicable Standard: FM3600 2011, FM3611 2004,

FM3615 2006, FM3810 1989,

Including Supplement 1 1995,

ANSI/NEMA 250 1991

Type of Protection: Explosion proof for Class I,

Division 1, Groups A,B, C and D;

Dust-ignition proof for Class II/III,
Division 1, Groups E, F,and G.

“SEAL ALL CONDUITS 18 INCHES.” “ WHEN
INSTALLED IN DIV.2, SEALS NOT REQUIRED”

Enclosure Rating: Type 4X
Temperature Code: T6
Ambient Temperature: -29 to 60°C (Integral Type

Vortex Flowmeter and
Remote Type Vortex Flow
Detector)

-40 to 60°C (Remote Type
Vortex Flow Converter)

Power Supply: 9 to 32Vdc (Integral Type Vortex

Flowmeter and Remote Type Vortex
Flow Converter)

Output Signal (Remote Type Vortex Flow Detector):

Output Signal to Converter; 30Vp-p,
100

μAp-p

Input/Output Signal (Remote Type Vortex Flow

Converter):

Input Signal from Flowmeter; 30Vp-p,
100

μAp-p

Electrical connection : ANSI 1/2 NPT female

(Special)

• Intrinsically Safe
Applicable Standard: FM3600: 1998, FM3610:

2010, FM3611: 2004,
FM3810: 2005,

NEMA 250: 1991,
ANSI/ISA-60079-0: 2009,
ANSI/ISA-60079-11: 2009,

ISA 60079-27: 2006

Type of Protection : Intrinsically Safe for Class I,

II, III, DIV.1, Groups A, B, C, D, E, F and G,

T4, and Class I, Zone 0, AEx ia IIB/IIC T4,
Entity, FISCO

Nonincendive for Class I, II, Div.2, Groups

A, B, C, D, F and G, Class III, DIV.1, Class I,
Zone 2, Group IIC, FNICO

Ambient Temperature :

–29 to +60°C (Integral Type Vortex

Flowmeter)

–29 to +80°C (Remote Type Vortex Flow

Detector)

–40 to +60°C (Remote Type Vortex Flow

Converter)

Indoors and Outdoors : Type 4X
Electrical Parameters : Intrinsically Safe

[Entity] Vmax=24V, Imax=250mA, Pi=1.2W,

Ci=3.52nF, Li=0

[FISCO (IIC)] Vmax=17.5V, Imax=380mA,

Pi=5.32W, Ci=3.52nF

[FISCO (IIB)] Vmax=17.5V, Imax=460mA,

Pi=5.32W, Ci=3.52nF, Li=0

Nonincendive
Vmax=32V, Ci=3.52nF, Li=0

Wiring

• Explosion proof

WARNING

• All wiring shall comply with National

Electrical Code ANSI/NFPA 70 and Local
Electrical Code.

• “SEAL ALL CONDUITS 18 INCHES”

“ WHEN INSTALLED DIV.2, SEALS NOT
REQUIRED”.

• Intrinsically Safe

NOTE

• The FM Approved Hand Held Communicator

may be connected at any point in the loop
between the digitalYEWFLO and the Control
Equipment.