<5. CONFIGURATION>

5-3

IM 01F06F00-01EN

Table 5.3

Function Block Execution Schedule of

the digitalYEWFLO

Index

Parameters

Setting (Factory Setting

in Parentheses)

269 (SM) MACROCYCLE_

DURATION

Repetition period of control
or measurement, i.e.,
macrocycle; to be set as a
multiple of 1/32 ms (32000
= 1 second)

276 (SM) FB_START_ENTRY.1

Start time of the AI1
block represented as the
elapsed time from the start
of each macrocycle; to be
set as a multiple of 1/32 ms
(0 = 0 ms)

277 (SM) FB_START_ENTRY.2

Start time of the PID block
(optional) represented as
the elapsed time from the
start of each macrocycle;
to be set as a multiple of
1/32 ms (9600 = 300 ms)

278 (SM)

to

289 (SM)

FB_START_ENTRY.3 to
FB_START_ENTRY.14

Not set.

A maximum of 29 ms is taken for execution of each
AI block. Arrange the communication schedule
for an AI block’s data that is to be transferred to its
downstream block in such a way that it starts after a
lapse of longer than 30 ms.
Figure 5.3 shows typical function block and
communication schedules for the loop shown in
Figure 5.2.

F0502.ai

FIC100

FIC200

FC100

FI200

digitalYEWFLO

#2

FI100

digitalYEWFLO

#1

Figure 5.2

Example of Loop Connecting Function

Blocks of Two digitalYEWFLOs with

Other Devices

FI103

FI100

FC100

FIC100

FC200

FIC200

FC100

FI200

FI200

Function

Block

Schedule

Commu-

nication

Schedule

OUT

IN

OUT

CAS_IN

BKCAL_OUT

BKCAL_IN

BKCAL_IN

BKCAL_OUT

IN

Unscheduled

Communication

Scheduled
Communication

F0503.ai

Macrocycle (Control Period)

Figure 5.3

Function Block Schedule and

Communication Schedule

When the control period (macrocycle) is set to more
than 4 seconds, set the following interval to be more
than 1% of the control period.

- Interval between “end of block execution”

and “start of sending CD from LAS”

- Interval between “end of block execution”

and “start of the next block execution”

5.4 Setting of Tags and Addresses

This section describes the steps in the procedure
to set the PD tags and node address in the
digitalYEWFLO. There are three states of Fieldbus
devices as shown in Figure 5.4, and if the state
is other than the lowest SM_OPERATIONAL
state, no function block is executed. Whenever
you have changed the PD tag or address of
a digitalYEWFLO, transfer its state to SM_
OPERATIONAL.

UNINITIALIZED

(No tag nor address is set)

Tag clear

Tag setting

INITIALIZED

(Only tag is set)

SM_OPERATIONAL

(Tag and address are retained, and
the function block can be executed.)

Address clear

F0504.ai

Address setting

Figure 5.4

Status Transition by Setting PD Tag and

Node Address