<APPENDIX 8. PID BLOCK>

A8-10

IM 01F06F00-01EN

A8.19 Example of Block

Connections

PID

BKCAL_IN

OUT

IN

AO

BKCAL_OUT

CAS_IN

AI

OUT

FA0808.ai

When confi guring a simple PID control loop by
combining a digitalYEWFLO with a fi eldbus valve
positioner that contains an AO block, follow the
procedure below to make the settings of the
corresponding fi eldbus function blocks:
1. Connect the AI block and PID block of the

digitalYEWFLO, and the AO block of the valve
positioner as shown above.

2. Set MODE_BLK.target of the PID block to

O/S, and then set GAIN, RESET, and RATE to
appropriate values.

3. Check that the value of MODE_BLK.actual of

the AI block is AUTO.

4. Set MODE_BLK.target of the AO block to

CAS|AUTO (meaning “CAS and AUTO”).

5. Check that the value of BKCAL_IN.status of the

PID block is not Bad.

6. Check that the value of IN.status of the PID

block is not Bad.

7. Check that AUTO is set in MODE_BLK.

permitted of the PID block.

8. Set MODE_BLK.target of the PID block to

AUTO.


When fi nishing all steps in order, the PID block and
AO block exchange the respective information and
initialize the cascade connection. Consequently,
the value of MODE_BLK.actual of the PID block
changes to AUTO and automatic PID control starts.