2. preparation, 2-1. cables, terminals and glands, 2. preparation -2 – Yokogawa EXA ISC202 2-wire Conductivity Transmitter/Analyzer User Manual

Page 34: 2-1. cables, terminals and glands -2

Advertising
background image

IM 12D06A03-01E

3-2 Installation and wiring

Figure 3-4. Internal view of EXA wiring compartment

3-2. Preparation

The power/output connections and the sensor connections should be made in accordance with figure 3-

5. The terminals are of a plug in style for ease of mounting.

To open the EXA for wiring:

1. Loosen the four frontplate screws and remove the cover.

2. The terminal strip is now visible.

3.

Connect the power supply. Use the gland on the left for this cable.

4.

Connect the sensor input, using the gland on the right (see fig. 3-5). Switch on the power.

Commission the instrument as required or use the default settings.

5. Replace the cover and secure frontplate with the four screws.

6. Connect the grounding terminals to protective earth.

7. The optional hose connection is used to guide the cables coming from an immersion fitting through a

protective plastic tubing to the transmitter.

Note that the sensor shall have a dielectric strength of 500 Vac with respect to earth and the intercon-

necting circuit to the transmitter shall be installed in such a way that mechanical damage is avoided.

3-2-1. Cables, terminals and glands

The EXA is equipped with terminals suitable for the connection of finished cables in the size range: 0.13

mA

Figure 3-3. Wall and pipe mounting diagram

56

2-Ш6.5

4-Ш10

70

200

77

115

Pipe mounting

(Vertical)

Pipe mounting

(Horizontal)

Nominal 50 A (O.D. Ø60.5 mm)

(7.87)

(2.75)

(0.26)

(2.20)

(0.4)

(3)

(4.5)

(2 inch pipe)

Unit: mm (inch)

Figure 3-5. Glands to be used for cabling

Grounding

terminal

Power/Output

cable gland

Sensor

cable glan

3.5

(0.14)

18.5 (0.72)

Unit: mm (inch)

+1

0

+1 0

PANEL CUTOUT

SPACING PANEL CUTOUT

Fig. 3-2b. Panel mounting using two (2) self-tapping screws

Advertising