Example of a connection with an upstream device, Wire – Yokogawa Standalone MW100 User Manual

Page 114

Advertising
background image

2-26

IM MW100-01E

Example of a Connection with an Upstream Device

You can connect the MW100 to an upstream device with an RS-232, RS-422A, or RS485
connection port.
For RS-232, use a converter. Refer to the following table for connections to most
converter terminals. For details, see the manual that came with the converter.

RS-422A/485 Port

Converter

SDA(–)

TD(–)

SDB(+)

TD(+)

RDA(–)

RD(–)

RDB(+)

RD(+)

SG

SHIELD

FG

EARTH

4-Wire

In general, a 4-wire connection is used with upstream devices. For a 4-wire connection,
the send and receive wires must be crossed.

Termination resistance (externally attached) 120 Ω 1/2 W or more

#

1

Do not connect termination resistance from #1 to #n–1.

Main unit

RS-422A/485

terminals

#

2

#

n

(

#

n32)

Termination resistance

(built-in: with switch)

Upstream

instrument

SG

RDB( + )

RDA( – )

SDB( + )

SDA( – )

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

2-Wire

On the RS-422A/485 terminal block, connect signals of the same polarity for sending and
receiving, and connect only two wires externally.

Termination resistance (externally attached) 120 Ω 1/2 W or more

#

1

Do not connect termination resistance from #1 to #n–1.

Main unit

RS-422A/485

terminals

#

2

#

n

(

#

n31)

Termination resistance

(built-in: with switch)

Upstream

instrument

SG

RDB( + )

RDA( – )

SDB( + )

SDA( – )

FG

SG

RD B

RD A

SD B

SD A

(SG)

(B)

(A)

(B)

(A)

FG

SG

RD B

RD A

SD B

SD A

(SG)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(B)

(A)

2.7 Connecting the RS-422A/485 Interface (/C3 Option)

Advertising