Reference junction compensation accuracy:

When measuring temperature greater than or equal to 0°C and
when the temperature of the input terminal is balanced

Type R, S, W: ±1°C

Type K, J, E, T, N, L, U, XK GOST: ±0.5°C

Type N (AWG14), PLATINEL, NiNiMo, WRe3-25,

W/WRe26: ±1°C

Note: Type B and PR40-20 internal RJC is fixed at 0°C

Maximum input voltage: DC voltage at 1-V range or less, TC, RTC, and DI (contact):

±10 VDC (continuous)

Other measurement ranges: ±120 VDC (continuous)

Normal-mode voltage: DC voltage, TC, DI (LEVEL): 1.2 times the range rating or less

(50/60 Hz, peak value including the signal component)

RTD 100 Ω: 50 mVpeak

RTD 10 Ω, 25 Ω, 50 Ω: 10 mVpeak

Normal-mode rejection ratio:

For integration time of 16.67 ms or more: 40 dB or more (50/60
Hz ± 0.1%)

For integration time of 1.67 ms: 50/60 Hz is not rejected.

The RTD and resistance ranges indicate the voltage conversion
value when current flows.

Common-mode voltage:600 VACrms (50/60 Hz), reinforced (double) insulation
Common mode rejection ratio (50/60 Hz ±0.1%, 500 Ω unbalanced between minus

measurement terminal and ground)

The RTD and resistance ranges indicate the voltage conversion
value when current flows.

When the integration time is 16.67 ms or more: 120 dB or more

When the integration time is 1.67 ms: 80 dB or more

Common-mode voltage between channels: 120 VACrms (50/60 Hz)
Noise rejection:

Rejection by the integrating A/D converter and the use of low pass
filters

Input resistance:

For DC voltage 1 V range or less and thermocouple range: 10
MΩ or less

For DC voltage 2 V range or higher: Approx. 1 MΩ

Insulation resistance: Between input and ground: 20 MΩ or more (500 VDC)
Input bias current:

10 nA or less (except for burnout setting)

Withstand Voltage:

1000 VAC (50/60 Hz) for one minute between input terminals

3700 VAC (50/60 Hz) for one minute between the input terminal
and earth terminal

Input signal source resistance:

DC voltage, thermocouple: 2 kΩ or less

RTD 50 Ω, 100 Ω types: 10 Ω per line or less

RTD 10 Ω, 25 Ω types: 1 Ω per line or less

Thermocouple burnout: Detection at a specified detection interval per measurement

interval and detection within the thermocouple range (detection
ON/OFF possible)

Up/Down setting is possible

2 kΩ or less normal, 200 kΩ or more disconnected

(shunt capacitance: 0.01 µF or less), detection current approx. 10
µA, detection time approx. 2 ms

Parallel capacity during RTD: 0.01 µF or less
Power consumption: Approx. 1.2 W
External dimensions: Approx. 57 (W) × 131 (H) × 151 (D) mm (including the terminal

cover)

Weight:

Approx. 0.5 kg.

Terminal type:

Clamp, terminal board is detachable

Applicable wire size: 0.14 to 1.5 mm

2

(AWG26 to 16)

5.5 10-CH, Medium-Speed Universal Input Module (MX110-UNV-M10) Specifications