Output types, Output method, Output range – Yokogawa Standalone MW100 User Manual

Page 66: Output update interval, Operation upon startup and errors, Output operation during calibration

Advertising
background image

1-52

IM MW100-01E

1.11 Functions of the 8-CH, Medium-Speed Analog

Output Module

The module has eight outputs for voltage or current.
An external power source (24 V) is required for current output.
For voltage output only, an external power source is not required.

Input terminal (clamp terminal)

Terminal cover

Output Types

Output Type

Notation

No output

SKIP

Analog output

AO

Output Method

Output Method

Notation

Actions

Transmission output

Trans

Outputs a voltage or current according to the

measured or computed data of the input channel

specified on the same unit. You can also produce

pattern output using the broken line input function.

Arbitrary output

Comm.Input

Outputs specified values based on values sent from

the PC.

Output Range

Output Range

Notation

Output range

Voltage

10 V

–10.000 V to 10.000 V

Current

20 mA

0.000 mA to 20.000 mA

Output Update Interval

The output is updated at 100-ms (minimum) intervals. It is not synchronized to the
measurement interval.

Operation upon Startup and Errors

See section 1.13, “Operation of the Eight-Channel Medium-Speed Analog Output Module
and the Eight-Channel Medium Speed PWM Output Module.”

Output Operation during Calibration

Calibration Condition

Output Operation

Channels being calibrated

Arbitrary output (output of calibration value)

Non-calibrated channels

Holds the output value (holds the value last output during steady

operation (see section 1.13))

Advertising