General specifications, General specifications -32 – Yokogawa Standalone MW100 User Manual

Page 245

Advertising
background image

5-32

IM MW100-01E

Initializing Settings

Two types of settings initialization are available.
Initialization of all settings:

Initializes all setting values and measured values on the main
unit. You can perform initialization through communication
commands, from the browser, or by resetting the dip switch
positions and turning ON the unit. However, when initialized using
communication commands or the browser, module recognition
information is not initialized.

Initialization of all settings excluding communication parameters:

All settings and measured values except for communication
parameters and module recognition information are initialized.
Communication commands are executed from the browser.

Initialization of the CF Card

Formats the CF card.
Format type:

Supports FAT12/FAT16, logical format only

CF card size:

2 GB maximum

File name format:

8.3 format

General Specifications

Operating temperature: –20 to 60°C
Operating humidity: 20 to 80% RH for –20 to 40°C

10 to 50% RH for 40 to 50°C

5 to 30% RH for 50 to 60°C

Power consumption: Approx. 8 W
Insulation resistance: Between power supply terminal and earth terminal: 20 MΩ or

more (500 VDC)

Withstand Voltage

AC power Between AC power supply terminal and earth
terminal: 1500 VAC (50/60 Hz) for one minute

DC power Between DC power supply terminal and earth
terminal: 1000 VAC (50/60 Hz) for one minute

External dimensions: Approx. 105 (W) × 131 (H) × 137 (D) mm
Weight:

Approx. 1 kg.

5.2 Main Module (MW100-E) Specifications