Explanation of Functions

1

2

3

4

5

App

Index

Output Operation through Setting Changes (Common)

Setting Changes (Contents)

Output Operation

Setting changes for operation

*1

Prev. value held → preset value Outputs the preset value the on

startup next time the power is

turned ON

Preset value → hold prev. value The last output value from the

previous operation is held for the

next time the power is turned ON

(outputs the output value active

when the power was last turned

OFF during the previous session)

Setting changes for operation

*1

Prev. value held → preset value Outputs the preset value the

upon error occurrence next time

an error occurs

Preset value → hold prev. value Holds the last output value active

before the error occurs for the

next time an error occurs.

Preset value setting changes

*2

No changes (as above)

Change setting of output ch from Enabled → Disabled

Holds the output value (last

output value)

*1 After changing settings, the changes take effect when measurement starts.
*2 Changes are also applied to inactive channels.

Output Operation through Setting Changes (Individually by Output Setting)

Output Setting

Setting Changes (Contents)

Output Operation

Transmission

Range setting AO: V ↔ mA

Output value held

output Within

changes

PWM: 1 ms ↔10 ms or interval (until the next output event)

units

Operation

Transmission within units →

setting changes arbitrary output

Span setting changes

Arbitrary

Range setting

AO: V ↔ mA

Output value held

output

changes

PWM: 1 ms ↔10 ms or interval (until the next output event)

Operation

Arbitrary output →

setting changes transmission within a unit

When the range settings of a PWM output module are changed, the output value is not held.

1.13 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output