Output types, Output method, Output range and output waveform – Yokogawa Standalone MW100 User Manual

Page 67: Pulse interval, Output update interval, Operation upon startup and error occurrence, App index

Advertising
background image

1-53

IM MW100-01E

Explanation of Functions

1

2

3

4

5

App

Index

1.12 Functions of the 8-CH, Medium-Speed PWM

Output Module

This module has eight outputs for pulse wave duty. A certain duty pulse waveform is output
according to the specified pulse interval. A pulse interval can be set for each channel.

Input terminal (clamp terminal)

Terminal cover

Output Types

Output Type

Notation

No output

SKIP

PWM Output

PWM

Output Method

Output Method

Notation Actions

Transmit

TRANS

Outputs a duty pulse waveform according to the measured or

computed data of the input channel specified on the same unit.

You can also produce pattern output using the broken line

input function.

Arbitrary output

COM

Outputs specified data based on the values sent from the PC.

Output Range and Output Waveform

Output range: 0.000 to 100.000%

Pulse interval

Output width

External

power supply

voltage

Duty=

Output width

Pulse interval

×100 [%]

Pulse Interval

1 ms to 300 s (can be set channel by channel)

Range

Notation

Setting Range

1 ms interval setting range

1 ms

1 ms to 30.000 s (can be set in units of 1 ms)

10 ms interval setting range

10 ms

10 ms to 300.00 s (can be set in units of 10 ms)

* The pulse interval can be set by determining the pulse interval coefficient.
The pulse interval coefficient is set from 1 to 30000.
Pulse interval = range × pulse interval coefficient

Output Update Interval

The output is updated at 100-ms (minimum) intervals. It is not synchronized to the
measurement interval.

Operation upon Startup and Error Occurrence

See section 1.13, “Operation of the 8-CH Medium-Speed Analog Output Module and the
8-CH Medium Speed PWM Output Module.”