Yokogawa Standalone MW100 User Manual

Page 75

Advertising
background image

1-61

IM MW100-01E

Explanation of Functions

1

2

3

4

5

App

Index

Preset Output upon Error (Firmware version R3.03 or later)

The following types are available.

Output

Notation

Description

Off

Off

No forced transition to Open/Close upon error.

Open

Open

Relay output Open (De-energize) upon error.

Close

Close

Relay output Close (Energize) upon error.

• The following conditions are required when the DO preset setting is enabled.

• The DO output type must be “Alarm DO”
• The Hold setting must be “Off”
• The Action must be “OR”

• The Energize/De-energize setting is enabled as in the standard specifications.
• Even if the preset setting is enabled for Alarm DO, DO preset output does not occur if

no alarm DO assignment from measurement or MATH channels is assigned.

• The computation error definition is for when the computed value is ±OVER.
• If multiple measurement or MATH channels are set for alarm DO output, the preset

output upon error is carried out if an error occurs on any one of the channels.

• Preset output upon error is cleared when errors are cleared on all measurement or

MATH channels set as alarm DO.

Preset Output upon Stop (Firmware version R3.03 or later)

The following types are available.

Output

Notation

Description

Off

Off

Holds previous value

Open

Open

Relay output Open (De-energize) upon error.

Close

Close

Relay output Close (Energize) upon error.

The stop detection/clear condition varies depending on the combination of channels set
for alarm DO.

Alarm DO setting

Stop detected

Stop cleared

Measurement channels only

Measurement stop

Measurement start

MATH channels only

Computation stop

Computation start

Measurement + MATH channels Computation stop

Computation start

If a stop is detected during preset output upon error, the preset output upon stop is
carried out.

1.14 Functions of the 10-CH, Medium-Speed Digital Output Module

Advertising