Execution errors, Execution errors -5, App index execution errors – Yokogawa Standalone MW100 User Manual

Page 197

Advertising
background image

4-5

IM MW100-01E

Troubleshooting and Maintenance

1

2

3

4

5

App

Index

Execution Errors

The code is divided into two parts which are displayed alternately on the 7-segment LED;
in the first part, the letter E appears in the left digit with the hundreds digit of the error
code to the right, and the second part consists of the last two digits of the error code.

Display

Possible Problem

Corrective Action

E201

Cannot execute due to different operation mode. Confirm the operation mode.

E202

Cannot execute when in setting mode.

Change the mode before execution.

E203

Cannot execute when in measurement mode.

Change the mode before execution.

E204

Cannot change or execute during memory sampling. Stop the save operation before executing.

E205

Cannot execute during MATH operation.

Stop the MATH operation before executing.

E206

Cannot change or execute during MATH operation. Stop the MATH operation before executing.

E207

Cannot change or execute while saving/loading

Execute after the settings are saved or loaded.

settings.

E209

Cannot execute while memory sample is stopped. Change the mode before execution.

E211

No relays for communication input found.

Check installation of relays and the relay output types.

E212

Initial balance failed.

Check the settings and wiring.

E213

No channels for initial balance found.

Check the target channels.

E214

No channels for transmission output found.

Specify channels for transmission output.

E215

No channels for arbitrary output found.

Specify channels for arbitrary output.

E221

No measurement channels found.

Check the measurement module, measurement group number,

measurement interval, and other settings.

E222

Invalid measurement interval.

Set the measurement interval so that: Meas. gr 1 ≤ meas. gr 2

≤ meas. gr 3

E223

Too many measurement channels.

The number of measurable channels during 10 ms

measurement is 10, and for 50 ms measurement, 30.

E224

No MATH channels found.

Check the MATH channel settings.

E225

Invalid MATH interval.

Set the MATH interval to measurement groups of 100 ms or

more. When measuring with measurement modules, set the

measurement group numbers on which to perform

measurement.

E226

Cannot start/stop MATH operation.

Cannot execute because MATH start is set for the level

detection action.

E227

Cannot start/stop recording.

Cannot execute because recording start is set for the level

detection action.

4.1 Error Display on the 7-Segment LED and Corrective Actions

Advertising