5-12

IM MW100-01E

File size:

Within approximately 10 Mbyte per file

File size calculation: File size (bytes) = header size

*1

+ data size

*2

*1

Header size (bytes) = Fixed length of 1448 + no. of recording

channels × 232

*2

Measurement data size (bytes) = no. of recording measurement

channels Ч 4 Ч no. of samples

Math data size (bytes) = no. of recording math channels Ч 6 Ч no. of

samples
No. of samples = Data length (s)/recording interval (s)

Ex.) Recording interval: 100 ms; no. of measurement channels, 24; data

length, 10 min.:

Header size = 1448 (bytes) + 24 × 232 (bytes) = 7016 (bytes)
Data size = 24 × 4 (bytes) × (600 (s)/0.1 (s)) = 576,000 (bytes)
File size = 7016 + 576000 = 583016 (byte)

≈ 569 (KB)

Guideline of the sample time for the different CF card sizes (when one type of recording

interval is used):

Number of

Saved CHs

Recording

Interval

Capacity of the CF card

128 MB

512MB

1 GB

10 CHs

10 ms

8.8 hours

35.3 hours

2.8 days

100 ms

3.7 days

14.8 days

28.9 days

500 ms

18.5 days

74 days

144 days

1 s

37 days

148 days

289 days

2 s

74 days

296 days

578 days

24 CHs

100 ms

36.8 hours

6.1 days

12.0 days

500 ms

7.7 days

30 days

60 days

1 s

15.3 days

61 days

119 days

2 s

30 days

122 days

239 days

60 CHs

100 ms

14.8 hours

2.4 days

4.8 days

500 ms

3.0 days

12.3 days

24.1 days

1 s

6.1 days

24.6 days

48 days

2 s

12.3 days

49 days

96 days

5 s

31 days

123 days

241 days

File division:

You can use the Event/Action function, status screen operations,
or communication commands to divide files at an arbitrary timing.

Valid when the recording start action is Direct and recording stop
action is Fullstop or Rotate.

File message:

The maximum number of characters that can be specified is 120.

The file message can be viewed when the file information is
displayed on the MW100 Viewer Software.

Write message:

During execution of the recording action, a message that
corresponds to the recorded data can be included in the file.

No. of characters in message: Up to 15

Messages: 6 (messages 1 to 5, and Free)

No. of write operations: Up to 30 per file

Operation upon failure recovery:

If a power failure occurs during recording, the data up to the
failure is restored upon recovery from the failure. The data after
recovery is recorded continuously to newly created files.

Operation when synchronizing time:

If time synchronization to SNTP is carried out during recording,
the time is saved to the recording log file.