Reference junction compensation accuracy:

When measuring temperature greater than or equal to 0°C

and when the temperature of the input terminal is balanced

Type R, S, W: ±1°C

Type K, J, E, T, N, L, U, XK GOST: ±0.5°C

Type N(AWG14), PLATINEL, NiNiMo, WRe3-25,

W/WRe26: ±1°C

Note: The internal reference junction compensation is fixed

to 0°C for type B and PR40-20

Maximum input voltage:

DC voltage at 1-V range or less, TC, RTC, and DI (contact):

±10 VDC (continuous)

Other measurement ranges: ±120 VDC (continuous)

Normal mode voltage:

DC voltage, TC, DI (LEVEL): 1.2 times the range rating or

less (50/60 Hz, peak value including the signal component)

RTD 100 Ω: 50 mVpeak

RTD 10 Ω, 25 Ω, 50 Ω: 10 mVpeak

Normal mode rejection ratio: For integration time of 16.67 ms or more: 40 dB or more

(50/60 Hz ± 0.1%)

For integration time of 1.67 ms: 50/60 Hz is not rejected

The RTD and resistance ranges indicates the voltage

conversion value when current flows.

Common-mode voltage:

600 VACrms (50/60 Hz), reinforced (double) insulation

Common mode rejection ratio (50/60 Hz ±0.1%, 500 Ω unbalanced between minus

measurement terminal and ground)

The RTD and resistance ranges indicates the voltage

conversion value when current flows.

When the integration time is 16.67 ms or more: 120 dB or more

When the integration time is 1.67 ms or more: 80 dB or more

Common-mode voltage between channels:

250 VACrms (50/60 Hz), reinforced (double) insulation

Noise rejection:

Rejection by the integrating A/D converter and the use of low

pass filters

Input resistance:

For DC voltage 1 V range or less and thermocouple range:

10 MΩ or less

For DC voltage 2 V range or higher: Approx. 1 MΩ

While measurement stopped: Approx. 1 MΩ

Insulation resistance:

Between input terminal and earth terminal: 20 MΩ or more

(500 VDC)

Input bias current:

10 nA or less (except for burnout setting)

Withstand voltage:

2300 VAC (50/60 Hz) for one minute between input terminals

3700 VAC (50/60 Hz) for one minute between the input

terminal and earth terminal

Input signal source resistance: DC voltage, thermocouple: 2 kΩ or less

RTD 50 Ω, 100 Ω types: 10 Ω per line or less

RTD10 Ω, 25 Ω types: 1 Ω per line or less

Thermocouple burnout:

Superposed electric current system, detection within the

thermocouple range (detection ON/OFF possible)

Up/Down setting is possible, current approximately 100 nA

2 kΩ or less normal, 10 MΩ or more disconnected

Effect on measurement accuracy: ±15 µV or less (not
including effect of signal source resistance)

Parallel capacity during RTD:

0.01 µF or less

Power consumption:

Approx. 3 W

External dimensions:

Approx. 57 (W) × 131 (H) × 151 (D) mm (including the

terminal cover)

Weight:

Approx. 0.5 kg.

Terminal type:

Clamp, detachable per channel

Applicable wire size:

0.2 to 2.5 mm

2

(AWG24 to 12)

5.4 4-CH, High-Speed Universal Input Module (MX110-UNV-H04) Specifications