App index – Yokogawa Standalone MW100 User Manual

Page 121

Advertising
background image

2-33

IM MW100-01E

Installation and W

iring

1

2

3

4

5

App

Index

If the first-order lag filter is applied to the input signal, low-pass filter frequency
characteristics shown in the figure below are attained.

Cutoff band

0dB

–3dB

Pass band

Frequency

Attenuation

Cutoff frequency

If the time constant of the first-order lag filter is set long, the cutoff frequency is lowered,
and frequency bandwidth that can be rejected is widened. Set an appropriate time
constant according to the frequency of the noise you wish to reject.

2.9 Measures Against Noise on the MW100 Data Acquisition Unit

Advertising