Measurement groups: Measurement channels can be divided into up to 3 groups by

module. The measurement interval must be the same for all
channels in the group.

Note that the equivalent of three modules worth of measurement
group settings are entered for the 30-CH Medium Speed DCV/
TC/DI Input Module. You cannot assign to different measurement
groups or change the measurement interval. You must assign all
three slots to the same measurement group.

MATH

Differential computation between channels:

Differential computation between arbitrary channels (DCV, TC,
RTD, DI, strain, resistance, pulse)

Linear scaling:

Scalable ranges: DCV, TC, RTD, DI, strain, resistance, pulse

Scaling range: –30000 to 30000

Scaling display range: –32000 to 32000

Decimal point position: Arbitrary

Units: Can be arbitrarily set using up to six characters

Linear scaling accuracy:

Linear scaling accuracy (digits)

= Measurement accuracy (digits) × expansion rate + 2 digits
(rounded up to the decimal place)

Note that the expansion rate = scaling span (digits) /
measurement span (digits)

(Ex.) Measuring range: 6 VDC (integral time of 16.67 ms or

more)
Measurement span: 1.000 to 5.000 V,
Scaling span: For a setting of 0.000 to 2.000

The measuring accuracy for 5.000 V input is as follows

according to the expression above.

± {(0.05% × 5.000 V + 2 digits) × (2000 / 4000) + 2 digits}

= ± {(0.0025 V + 2 digits) × 0.5 + 2 digits}

= ± 4.25

5 digits (rounded up to the decimal place)

Thus the measuring accuracy when scaling = ± 5 digits

MATH Function Specifications (/M1 Option)

The following MATH functions can be added with options.

Number of MATH channels: 60 (can also be used for communication input)

Number of channels for communication input: 240

Computation start/stop:

Execution of computation starts and stops according to

user commands (Start/Stop key, Event/Action function, or

communication commands).

Note that computed data includes the data when

computation started and stopped.

MATH interval:

Specify one from among the measurement group numbers,

and perform computation. However, measurement intervals

of 10 ms or 50 ms cannot be specified.

Computation reset/clear:

You can reset or clear the computed data via the Event/

Action function, communication commands, or requests from

operations in the monitor screen.

Group reset:

Only the MATH channels set by group, up to seven groups,

are reset by the Event/Action function. Can be executed

using the Event/Action function.

5.2 Main Module (MW100-E) Specifications