Yokogawa Standalone MW100 User Manual
Page 208

4-16
IM MW100-01E
For -NDI
Connect CH2 only
Setting switch
R2
R4
R1
R3
ON
1 2 3 4 5
1
2
3
4
5
6
7
8
OFF
SW
Bridge head
(701955 or 701956)
SW1
OFF
SW2
OFF
SW3
OFF
SW4
ON
SW5
OFF
• When calibrating the output range of the 8-CH, Medium-Speed Analog Output module
All eight channels are calibrated at Zero (0 V) and Full (10 V).
Digital multimeter
H
L
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Calibration of Temperature Measurements using Thermocouples
Required Instruments
• DC Voltage/Current Standard
Must meet the following specifications (5520A by FLUKE or equivalent):
Output accuracy: ±(0.005%+1 µV) or less
• 0 °C reference temperature device
Must meet the following specifications (ZC-114/ZA-10 by Coper Electronics or
equivalent)
Standard temperature stability accuracy: ±0.05°C or less
4.4 Calibration