Yokogawa Standalone MW100 User Manual

Page 208

Advertising
background image

4-16

IM MW100-01E

For -NDI

Connect CH2 only

Setting switch

R2

R4

R1

R3

ON

1 2 3 4 5

1

2

3

4

5

6

7

8

OFF
SW

Bridge head

(701955 or 701956)

SW1

OFF

SW2

OFF

SW3

OFF

SW4

ON

SW5

OFF

• When calibrating the output range of the 8-CH, Medium-Speed Analog Output module
All eight channels are calibrated at Zero (0 V) and Full (10 V).

Digital multimeter

H

L

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15

Calibration of Temperature Measurements using Thermocouples

Required Instruments

• DC Voltage/Current Standard
Must meet the following specifications (5520A by FLUKE or equivalent):
Output accuracy: ±(0.005%+1 µV) or less
• 0 °C reference temperature device
Must meet the following specifications (ZC-114/ZA-10 by Coper Electronics or

equivalent)

Standard temperature stability accuracy: ±0.05°C or less

4.4 Calibration

Advertising