Yokogawa Standalone MW100 User Manual

Page 84

Advertising
background image

1-70

IM MW100-01E

• Special computation processing (excluding TLOG and CLOG computation) for

measurement channels

Reference Channel Status Notation Process Description

Abnormal input value

Error

Computed result is an error

Skip

Continue computation using previous value of

channel on which abnormal value was input

Overflow value

Over

Compute using overflow value

Skip

Continue computation using previous value of

channel on which overflow value resulted

Limit

*1

The overflow value is replaced with the upper or

lower limit, and computation continues

*1 The lower/upper limit value replaced on the measurement channel differs depending on the

computation type.

Measurement channel: Measurement range upper and lower limit

Scaled measurement channel: Upper and lower limit of scaling

• Special processing for reference channels of TLOG and CLOG computations
TLOG Computation

Reference

Channel Status

Notation

MAX

MIN

P-P

AVE

SUM

PSUM

Abnormal input

value

Error

Computed result is an error

*3

Skip

Current TLOG computation is skipped

Overflow value

Error

Computed with the

overflow value as-is

Computed

result is a

+OVER

*2

Computed result is an error

*3

Skip

Current TLOG computation is

skipped

Limit

The overflow value is replaced

with the upper or lower limit,

and computation continues

*4

CLOG Computation
Firmware version R3.04

Refaerence

Channel Status Notation

MAX

MIN

P-P

AVE

Abnormal input

value

Error

Computed result is an error

Skip

Computation is carried out without the channel on which the

abnormality occurred

Overflow value

Error

Computation

occurs with the

overflow value as-

is

Computed result

is +Over

*2

Computed result is

an error

Skip

Computation is carried out without the channel on which the

overflow occurred

Limit

The overflow value is replaced with the upper or lower limit,

and computation continues

*4

Firmware version R3.03 or earlier

Reference

Channel Status Notation

MAX MIN

P-P

AVE

Abnormal input

value

Error

Computed result is an error

Skip

Computation is carried out without the channel on which the

abnormality occurred

Overflow value

Error

Computed result is an error

Skip

Computed with the

overflow value as-is

Computation is carried out without the

channel on which the overflow occurred

Limit

The overflow value is replaced with the

upper or lower limit, and computation

continues

*4

*2 If the data is plus over only or minus over only, the computed result is an error
*3 Once an error occurs, computed results continue to be errors until computation is cleared
*4 The lower/upper limit value replaced on the reference channel differs depending on the input

type.

Measurement channel

Measurement range upper and lower limit

Scaled measurement channel: Upper and lower limit of scaling
Computation channel:

Span upper limit and lower limit

1.15 MATH Function (/M1 Option)