Yokogawa Standalone MW100 User Manual

Page 72

Advertising
background image

1-58

IM MW100-01E

Output Operation during an Abnormality (by Output Setting)

Output Setting Abnormal Status

Output Operation

Transmission Referenced input channels are +Over Outputs a value +5% of the specified
output within units

span of the output channel

*1

Referenced input channels are –Over Outputs a value –5% of the specified

span of the output channel

*1

Referenced input channel is illegal

Operation upon errors

(input module removed)

Referenced input channel is set to Skip

Referenced input channel is Invalid

(math error in Differential computation)

Internal communication error

Output value held (occurs immediately

after an internal communication error,

but there is a recovery action

*2

)

CPU abnormality

Operation upon errors

Arbitrary output Internal communication error

Output value held (occurs upon an

internal communication error, but there

is a recovery action

*2

)

CPU abnormality

Operation upon errors

*1 PWM output may not always reach +5% (+Over)/–5%(–Over).
*2 See “Output Operation after Recovery from an Abnormality.”

Output Operation after Recovery from an Abnormality (by Output Setting)

Output Setting Abnormality Recovery

Output Operation

Transmission Referenced input module recovers

Operation upon errors → transmission

output within units (removed input modules are inserted) output

Referenced input channel changed

from Skip to Measurement range

Referenced input channel is restored

from Invalid (math error in Differential

computation) to normal

Recover after internal communication If the error recovery time is 10 s or

error

more; operation upon error →

operation upon power ON→

Transmission output

If the error recovery time is within 10 s;

operation upon startup → transmission

output

CPU abnormality (does not recover) Operation upon errors

Arbitrary output Recover after internal communication If the error recovery time is 10 s or

error

more; operation upon error →

operation upon power ON→ arbitrary

output*

If the error recovery time is within 10

s; operation upon startup → arbitrary

output*

CPU abnormality (does not recover) Operation upon errors

* Executed by arbitrary output from the PC after recovering from the error.

1.13 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output

Module

Advertising