Attributes, Actions – HP NonStop G-Series User Manual

Page 110

Advertising
background image

Location in OSM Tree: System > Group > Module > Fan

Slot Location: Fan CRUs are located in slots 25 and 26 on the appearance side of processor
enclosures.

Note: The fans built into the S7400, S7x000, and S86000 power supplies (slots 31 and 32) are

field-replaceable units (FRUs) and must be serviced only by your service provider.

Example: Fan (1.1.22)

Attributes

Fan

Service State

Displayed in the Attributes tab and Attributes dialog box only if attention or service is
required.

Values

Physical

Manufacturer Identifies the manufacturer of the component.

Power State

Whether the component is powered on.

Values

Logical

Enabled State The current state of the fan as known to the operating system.

Values

Rotations Sensor

Normal Minimum Value

The minimum acceptable fan speed is 1800 RPM. If the speed falls below
1800, an alarm is generated.

Current Value

The current fan speed, measured in rotations per minute (RPM).

Alarms are generated if the speed of the fan falls below 1800 (minimum
RPM) or rises above 5800 (maximum RPM).

Normal Maximum Value

The maximum acceptable fan speed is 5800 RPM. If the speed rises
above 5800, an alarm is generated.

Actions

Enable/Disable

Restores or stops power to the fan. After servicing the fan or its associated PMCU, perform the
Enable action.

Parameter: Enabled (true = enabled, false = disabled)