Other Rail Voltage

The voltage of the Other Rail, which connects the PMF2/IOMF2
CRU to the other power supply in the enclosure (to provide power in
the event of a problem with the Main Rail power supply).

Other Rail Voltage After Fuse

The current voltage on the Other Rail of the PMF2 CRU, measured
after the fuse.

Storage ASIC

Initialization State

The status of the storage ASIC in the CRU.

Values: Initialized, Uninitialized, Unknown

Actions

Disable ServerNet Port

Disables the specified ServerNet port on this CRU. Perform this action only as directed by OSM
alarm repair actions.

Parameter: Port Number

Enable ServerNet Port

Enables the specified ServerNet port on this CRU. Perform this action only as directed by OSM
alarm repair actions.

Parameter: Port Number

Force Power Off

This action is not supported for this CRU type. See the

Prepare to Power Off

action.

Power Off

This action is not supported for this CRU type. See the

Prepare to Power Off

action.

Prepare to Power Off

Performs a precautionary check to make sure you can safely remove the CRU. This check makes
sure:

The other PMF2 CRU in this enclosure exists and is powered on

The status of the power supply for the other PMF2 CRU in this enclosure is OK

The other PMF2 CRU in this enclosure has ServerNet connectivity

The processor in the other PMF2 CRU in this enclosure has connectivity to CPU 0 or CPU 1

If the check confirms that it is safe to power off, these preparatory steps are performed: