C13874, C13874 | cip connections timeout time, C13875 – Lenze E84AYCEO User Manual

Page 119: C13875 | cip connections run/idle flag, C13880, C13880 | monitoring reaction, Rised here, C13880/1, C13880/4, C13880/2

Advertising
background image

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

119

13

Parameter reference

13.1

Parameters of the communication module

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13874

C13875

C13880

Parameter | Name:

C13874 | CIP Connections Timeout Time

Data type: UNSIGNED_32

Index: 10701 = 0x29CD

Display of the timeouts (ms) of the CIP connections
Display range

(min. value | unit | max. value)

0

ms

4294967295

Subcodes

Info

C13874/1

Timeout time of CIP connection 1

...

...

C13874/8

Timeout time of CIP connection 8

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13875 | CIP Connections RUN/IDLE Flag

Data type: UNSIGNED_16

Index: 10700 = 0x29CC

Display of the run and idle flags of the CIP connections
Selection list

(read only)

0 Nonexistent
1 IDLE
2 RUN

Subcodes

Info

C13875/1

RUN/IDLE flag - CIP connection 1

...

...

C13875/8

RUN/IDLE flag - CIP connection 8

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13880 | Monitoring Reaction

Data type: UNSIGNED_8

Index: 10695 = 0x29C7

Setting of the monitoring response in the event of a

Fault with regard to EtherNet/IP communication ( 88)

(Mapping of the Lenze object

Lenze Class (101 / 0x65) ( 155)

)

A change in the monitoring response becomes immediately effective.
Selection list

0 No response
1 Fault
3 Quick stop by trouble
4 Warning Locked
6 Information

Subcodes

Lenze setting

Info

C13880/1

0: No Response

Idle Mode

C13880/2

3: Quick stop by trouble

Fault Mode

(only for "exclusive owner" connections)

C13880/3

0: No Response

Expl. message timeout

C13880/4

0: No Response

Overall Ethernet communication timeout

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Advertising