5 external voltage supply, External voltage supply, External voltage supply ( 33) – Lenze E84AYCEO User Manual

Page 33: 5installation

Advertising
background image

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

33

5

Installation

5.2

Electrical installation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.5

External voltage supply

The communication module can be externally supplied with voltage via separate supply cables at

the 2-pin plug connector X258.

The external voltage supply of the communication module is necessary if the power supply for the

basic device fails but communication via the fieldbus is to be maintained.
The parameters of a standard device separated from the mains cannot be accessed.

Wiring of the X258 plug connector

[5-11] Wiring of the 2-pin plug connector with spring connection

How to wire the plug connector with spring connection:

1. Press a screwdriver into the notch below the terminal and keep it pressed.
2. Place the supply cable in the terminal.
3. Remove the screwdriver from the notch.

Assignment of the X258 plug connector

Note!

With external voltage supply, always use a separate power supply unit, safely separated

to EN 61800-5-1 in every control cabinet (SELV/PELV).

Stop!

Only wire the plug connector if the standard device is disconnected from the mains.

E84AYCXX010

Name

Description

+

U = 24 V DC (20.4 V - 0 % ... 28.8 V + 0 %)

I = 140 mA

-

Reference potential for the external voltage supply

Advertising