Parameter data transfer (explicit messages)

9.2

Read parameters

86

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2

Read parameters

In order to read out Lenze code C00011 (reference speed) of the Inverter Drive 8400 by means of

explicit message transfer, for example, the following settings are necessary:

Settings

Value / description

Message Type

"CIP Generic"

Service Type

"Get Attribute Single" (service code "0x0E")

Class

"6E" (access to to Lenze code)

Instance

"11" = Lenze code C00011 of Inverter Drive 8400

Attribute

"1" = Subcode of the Lenze code

If the corresponding Lenze code does not have a subcode, the value ’1’ must

be entered here.

Destination

Variable in the PLC program the drive data will be copied to.

When reading code C00011, make sure that the tag used as destination is a

single word in UINT16 format.