14

Implemented CIP™ objects

14.1

General CIP objects

136

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Instance error messages

Supported service codes

Error

code

[hex]

Extended

code

[hex]

Error designation

Description

0x000

-

SUCCESS

No error

0x001

0x106

OWNERSHIP_CONFLICT

The connection could not be established because another

connection has already occupied the required resources. It is

only possible to establish an "exclusive owner" connection to

the adapter.

0x001

0x119

NON-

LISTEN ONLY CONNECTION

NOT OPENED

The connection could not be established because there is no

"non-listen only" connection (input only, exclusive owner).

The "non-listen only" connection must be of the "multicast"

connection type.

0x001

0x127

INVALID_ORIGINATOR_TO_

TARGET_SIZE

The resulting length of the ports mapped in the receive

object PDO_RX0 does not correspond to the number of data

bytes of the assembly object instance 110 (0x6E, Custom

Output) defined in the scanner.

0x001

0x128

INVALID_TARGET_TO_

ORIGINATOR_SIZE

The resulting length of the ports mapped in the transmit

object PDO_TX0 does not correspond to the number of data

bytes of the assembly object instance 111 (0x6F, Custom

Input) defined in the scanner.

0x001

0x204

UNCONNECTED_REQUEST_

TIMED_OUT

The adapter does not respond to the establishment of the

connection.

• There might be no physical connection.

• The adapter is switched off.

• The adapter has an invalid IP configuration.

0x001

0x320

ACCESS_CONTENTION

Manufacturer-specific error:

• The configurations of the assembly input and output

objects are mixed up.

• The connection could not be established because another

connection has already occupied the required resources.

It is only possible to establish an "exclusive owner"

connection to the adapter.

0x001

0x111

ROUTER_EXT_ERR_RPI_

NOT_SUPPORTED

The RPI set for a connection is not supported.

• Min. class 1 RPI = 4 ms

• Min. class-3-RPI = 10 ms

0x001

0x112

RROUTER_EXT_ERR_RPI_

VALUE_NOT_ACCEPTABLE

The RPI set for a connection is not supported.

• Min. class 1 RPI = 4 ms

• Min. class-3-RPI = 10 ms

0x001

0x123

ROUTER_EXT_ERR_INVALID_

TO_ CONNECTION_TYPE

The output image connection type is invalid or not

supported.

0x001

0x124

ROUTER_EXT_ERR_INVALID_

TO_ CONNECTION_TYPE

The input image connection type is invalid or not supported.

0x001

0x12A

ROUTER_EXT_ERR_INVALID_

CONSUMING_PATH

The path specification for the output data from the scanner

is invalid.

0x001

0x12B

ROUTER_EXT_ERR_INVALID_

PRODUCING_PATH

The path specification for the input data to the scanner is

invalid.

Service code

[hex]

Name

Description

0x54

Forward_Open

Opens a CIP connection from the PLC to the target drive.

0x4E

Forward_Close

Closes a CIP connection from the PLC to the target drive.

0x0E

Get_Attribute_Single

Outputs the value of a certain attribute.