8i/o data transfer (implicit messages) – Lenze E84AYCEO User Manual

Page 73

Advertising
background image

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

73

8

I/O data transfer (implicit messages)

8.6

I/O configuration with »RSLogix 5000« version 20 or higher

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.6

I/O configuration with »RSLogix 5000« version 20 or higher

The following example describes the I/O configuration of the Allen-Bradley 1769-L32E

CompactLogix controller using the Rockwell »RSLogix 5000« programming software from version

20.
From software version 20 onwards,

EDS files

( 37)

are used for the I/O configuration.

How to carry out the I/O configuration, taking the CompactLogix controller 1769-L32E

with »RSLogix 5000« as an example:

1. Use the "EDS Hardware Installation Tool" item to import the

EDS files

( 37)

of the

EtherNet/IP nodes.

In »RSLogix 5000«, the dialog for the "EDS Hardware Installation Tool" is self-explanatory

and not described further in this documentation.

2. Click the I/O Configuration folder in the configuration tree.

For the 1769-L32E CompactLogix controller, the I/O configuration already includes a local

Ethernet port.
If a SoftLogic or ControlLogix controller is used, an Ethernet port scanner needs to be added

to the configuration.

Advertising