I/O data transfer (implicit messages)

8.6

I/O configuration with »RSLogix 5000« version 20 or higher

78

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10. Open the "New Module" dialog window, select the Connection tab and set further

properties.

"Name" displays the name of the connection set under 8..

The example shows an "Exclusive Owner - Custom" connection. According to this, the name of an

"AC Drive Profile" connection may be displayed here too.

Required settings

Optional settings

Settings

Description

Requested Packet

Interval (RPI)

Set RPI 4.0 ms. (Standard: 10 ms)

The RPI [ms] specifies the intervals for the I/O data exchange between the drive

(adapter) and the controller (scanner).

Input type

Select the "Multicast" input type.

• The input data is sent from the adapter to the scanner by means of multicast

telegrams.

• Other scanners can access this data in addition to the currently configured

scanner ("Listen only" or "Input only" connections).

Settings

Description

Inhibit module

This option serves to interrupt or inhibit the communication to the adapter.

Major Fault On

Controller If Connection

Fails While In Run Mode

This option serves to put the controller into the error status if the EtherNet/IP

connection to the drive fails while the controller is running.