Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

45

6

Commissioning

6.4

Setting the IP configuration of the Inverter Drive 8400

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.4.2

Setting via codes in the »Engineer«

You can also set the IP parameters manually in the »Engineer« under the Settings tab. The values

will be transferred to the corresponding codes.

How to activate changed settings in the »Engineer«:

1. Execute device command C00002 = "11: Save all parameter sets".

The current IP configuration is stored in the memory module of the drive.

2. Carry out a "Type 0 reset" for the

Identity Object (1 / 0x01)

( 126)

of the node, or switch the

voltage supply of the communication module off and on again.

Settings / Display

Description

Rotary coding switch

Display of the value set by means of the rotary coding switches (

C13920

).

Setting node addresses by means of rotary coding switches ( 40)

IP Config Control

Selection (

C13005

) of how the IP configuration is to be made:

0: The IP configuration currently stored in the communication module is

used.

1: The IP configuration is assigned by a BOOTP server using the BOOTP.

2: The IP configuration is assigned by a DHCP server using the DHCP.

IP Address

Setting of the IP address (

C13000

)

Subnet mask

Setting of the subnet mask (

C13001

)

Gateway Address

Setting of the gateway address (

C13002

)

Multicast IP Start Address

Setting of the Multicast IP start address (

C13006

)

Setting the multicast configuration ( 48)

Multicast Config TTL Value

Setting of the multicast TTL value (

C13019

)