2 control supervisor object (41 / 0x29), Control supervisor object (41 / 0x29) ( 150), 14 implemented cip™ objects – Lenze E84AYCEO User Manual

Page 150

Advertising
background image

14

Implemented CIP™ objects

14.3

"AC Drive Profile" objects

150

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

14.3.2

Control Supervisor Object (41 / 0x29)

The "Control Supervisor Object" describes all management functions of the devices used to control

the motor.

Class attributes

Instance attributes

Attribute

ID

Service

Name

Data type

Value

1

Get

Revision

UINT

1 (0x0001)

2

Get

Max. Instance

UINT

1 (0x0001)

3

Get

Number of Instances

UINT

1 (0x0001)

Attribute

ID

Service

Name

Data type

Value

1

Get

NumAttr

USINT

Number of supported attributes

2

Get

Attributes

ARRAY of

USINT

Listing of the supported attributes

3

Set

Run1

BOOL

Run/stop can be controlled via a local setting

on the device or terminal, or via the network

(see attribute "NetCtrl").

The relationship between Run1, Run2 and

the trigger events is described in the

Run/

stop event ( 151)

section.

4

Set

Run2

BOOL

5

Set

NetCtrl

BOOL

Run/Stop control

• 0: Run/stop control via local setting on

the device or terminal

• 1: Run/stop control via network (e.g. from

the scanner)

6

Get

State

USINT

• 0: Manufacturer-specific

• 1: Startup

• 2: Not_Ready

• 3: Ready

• 4: Enabled

• 5: Stopping

• 6: Fault_Stop

• 7: Faulted

7

Get

Running1

BOOL

• 0: Other status than listed under ’1’

• 1: [Enabled and Run1] or

[Stopping and Running1] or

[Fault_Stop and Running1]

8

Get

Running2

BOOL

• 0: Other status than listed under ’1’

• 1: [Enabled and Run2] or

[Stopping and Running2] or

[Fault_Stop and Running2]

9

Get

Ready

BOOL

• 0: Other status than listed under ’1’

• 1: Ready or Enabled or Stopping

10

Get

Faulted

BOOL

• 0: No errors

• 1: Errors have occurred

11

Get

Warning

BOOL

• 0: No warnings

• 1: Warnings have occurred

12

Set

FaultRst

BOOL

• 0  1: Reset error

• 0: No Response

Advertising