8

I/O data transfer (implicit messages)

8.5

I/O configuration with »RSLogix 5000« version 19 or lower

70

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5. Go to the "New Module" dialog window and define the properties of the newly added

device .
The terms "input" and "output" refer to the point of view of the scanner:

• Assembly input objects (input) are sent from the adapter to the scanner.
• Assembly output objects (output) are sent from the scanner to the adapter.


Settings for Lenze technology applications or user-definable parameter sets:

If you use a Lenze technology application or an individual parameter set in the drive, you

can exchange up to 16 user-definable words (INT) via the ports MCI_IN and MCI_OUT using
the assembly object instances

"Input = 111" and

"Output = 110".

Go to

"Configuration" and enter the Assembly instance "130" and the Size "0".