Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

59

8

I/O data transfer (implicit messages)

8.2

Technology applications (TA) / drive profiles

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.2.2

"AC Drive Profile" application

From inverter drive version V13.00 and communication module version V01.02, the EtherNet/IP-

specific "AC Drive Profile" is supported.
The standard device code C00005 = "1100: AC Drive Profile" serves to select the "AC Drive Profile"

application.
The "AC Drive Profile" contains ...

• the data basis for motor parameters,
• management functions of the motor control devices,
• Device-specific functions of the drive, e.g. speed ramps, torque control etc.

For using the "AC Drive Profile", the following assembly object instances in the host (scanner) have

to be used:

See also:

Assembly Object (4 / 0x04)

( 129)

"AC Drive Profile" objects

( 148)

Tip!
Here you will find information on configuring with the »RSLogix 5000« programming

software from Rockwell:

I/O configuration with »RSLogix 5000« version 19 or lower

( 68)

I/O configuration with »RSLogix 5000« version 20 or higher

( 73)

Instance ID

Assembly object instance

[dec]

[hex]

20

0x14

Basic Speed Control Output

Outputs: From the scanner to

the adapter

21

0x15

Extended Speed Control Output

22

0x16

Speed and Torque Control Output

23

0x17

Extended Speed and Torque Control Output

70

0x46

Basic Speed Control Input

Inputs: From the adapter to

the scanner

71

0x47

Extended Speed Control Input

72

0x48

Speed and Torque Control Input

73

0x49

Extended Speed and Torque Control Input