Ethernet/ip: invalid ip parameters [0x01bc6533, Ethernet/ip: fault mode [0x01bc8111, Ethernet/ip: explicit message timeout [0x01bc8112 – Lenze E84AYCEO User Manual

Page 99: Ethernet/ip: overall ethernet timeout [0x01bc8114, Ethernet/ip: ethernet cable pulled out [0x01bc8121, Ethernet/ip: invalid ip, Parameters [0x01bc6533, Is output, 0x01bc6533, 0x01bc8111

Advertising
background image

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

99

12

Error messages

12.2

Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

EtherNet/IP: Invalid IP parameters [0x01bc6533]

EtherNet/IP: Fault Mode [0x01bc8111]

EtherNet/IP: Explicit Message Timeout [0x01bc8112]

EtherNet/IP: Overall Ethernet Timeout [0x01bc8114]

EtherNet/IP: Ethernet cable pulled out [0x01bc8121]

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

One or more IP parameters are faulty.

Check and correct IP configuration.

Setting the IP configuration of the Inverter Drive 8400

( 42)

Response (Lenze setting printed in bold)

Setting:

C13880/2

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Connection to scanner has been interrupted.

• Controlling I/O connection failed by timeout.

• Within the timeout time for implicit messages

parameterised by the scanner, no "implicit messages"

have been received.

• Check cables and terminals.

• Plug in the network cable into the Ethernet port.

• Check Requested Package Interval (RPI) of I/O

connection.

• Increase timeout time for implicit messages.

Response (Lenze setting printed in bold)

Setting:

C13880/3

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Connection to scanner has been interrupted.

• Failure of an explicit connection

• Within the timeout time for explicit messages

parameterised by the scanner, no "explicit messages"

have been received.

• Check cables and terminals.

• Plug in the network cable into the Ethernet port.

• Check Requested Package Interval (RPI) of the explicit

connection.

• Increase timeout time for explicit messages.

Response (Lenze setting printed in bold)

Setting:

C13880/4

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Failure of »Engineer« communication via Ethernet

• When the time set in

C13881

has expired, there is no

access via the »Engineer«.

• Check cables and terminals.

• Plug in the network cable into the Ethernet port.

• Increase the overall Ethernet timeout time in

C13881

.

Fault with regard to EtherNet/IP communication

( 88)

Response (Lenze setting printed in bold)

Setting: not possible

None  system fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Network cable has been detached from the Ethernet

terminal.

• Network cable (plug) is defective.

• Plug the network cable into the Ethernet terminal.

• Check the network cable (plug) and replace it if

necessary.