4 lenze objects, 1 lenze class (101 / 0x65), Lenze class (101 / 0x65) ( 155) – Lenze E84AYCEO User Manual

Page 155: 14 implemented cip™ objects

Advertising
background image

Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17

155

14

Implemented CIP™ objects

14.4

Lenze objects

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

14.4

Lenze objects

14.4.1

Lenze Class (101 / 0x65)

The "Lenze Class (101 / 0x65)" enables the access to the adjustable error responses to EtherNet/IP

errors which can be set in code

C13880

.

Class attributes

Instance attributes

Note

The attributes of this class are described in the EDS file. Using the »RSNetWorx«

Rockwell software, the attributes can thus be directly set under "Parameters" in the

properties dialog of the EtherNet/IP node.

Attribute

ID

Service

Name

Data type

Value

1

Get

Revision

UINT

2 (0x0002)

2

Get

Max. Instance

UINT

1 (0x0001)

Attribute

ID

Service

Name

Data type

Value

1

Get

No. of supported Attributes

USINT

6 (0x0006)

2

Get

Attribute List

USINT

1 (0x0001) ... 6 (0x0006)

3

Get / Set Reaction on Idle Mode

USINT

Corresponds to the value in

C13880/1

:

• 0 = no response

• 1 = error

• 4 = warning locked

4

Get / Set Reaction on Fault Mode

USINT

Corresponds to the value in

C13880/2

:

• 0 = no response

• 1 = error

• 4 = warning locked

5

Get / Set Reaction on Expl. Msg. TO

USINT

Corresponds to the value in

C13880/3

:

• 0 = no response

• 1 = error

• 4 = warning locked

6

Get / Set Reaction on I/O Timeout

USINT

Corresponds to the value in

C13880/4

:

• 0 = no response

• 1 = error

• 4 = warning locked

Advertising