Technical data

General data and operating conditions

3

l

102

EDK82EV222 DE/EN/FR 13.0

Ambient conditions

DC mains connection

Max. mains voltage range

450 V − 0 % ... 740 V + 0 %

E82xV251K2... and E82xV371K2...

not possible

E82xV551K2... to E82xV752K2...

140 V − 0 % ... 370 V + 0 %

E82xV551K4... to E82xV903K4...

450 V − 0 % ... 775 V + 0 %

Operation at rated power

450 V − 0 % ... 625 V + 0 %

Operation at an increased rated
power

Operating conditions

The DC voltage must be symmetrical to PE.
The controller will be destroyed if the +U

G

conductor or −U

G

conductor is earthed.

Motor connection

Length of the motor cable

< 50 m

shielded

< 100 m

unshielded

For rated mains voltage and switching frequency

£ 8 kHz

without additional output filters.
For compliance with EMC regulations, the permissible cable
length may be different.

Mechanical

Vibration resistance
(9.81 m/s

2

= 1 g)

Germanischer Lloyd
5 ... 13.2 Hz

Amplitude ±1 mm 13.2 ... 100 Hz:
acceleration resistant up to 0.7 g

IEC/EN 60068−2−6
10 ... 57 Hz

Amplitude 0.075 mm 57 ... 150 Hz:
acceleration resistant up to 1 g

Mounting conditions

Mounting place

In the control cabinet

Mounting position

Vertical

Dimensions,
free spaces

^

Chapter "Mechanical installation"

Weights

^

Chapter "Technical data", "Operation at rated power" or

"Operation at increased rated power"