Troubleshooting and fault elimination

Fault elimination

Fault messages

8

l

161

EDK82EV222 DE/EN/FR 13.0

Remedy

Cause

Fault

PC

1)

Keypad

OH

a

50

Heatsink
temperature > +85
°C

Ambient temperature is too high

Allow controller to cool and provide
for better ventilation

OH

e

Heatsink
temperature > +80
°C

Heatsink is very dirty

Clean heatsink

OH

e

Heatsink
temperature > +80
°C

Impermissible high currents or
frequent and too long
acceleration processes

l

Check drive dimensioning

l

Check load, replace
rough−running, defective
bearings, if necessary

OH3

a

53

PTC monitoring
(TRIP)
(display when
C0119 = 1 or 4)

Motor too hot due to
impermissible high currents or
frequent and too long
acceleration processes

Check drive dimensioning

No PTC connected

Connect PTC or switch off monitoring

OH4

a

54

Controller
overtemperature

Controller is too hot inside

l

Reduce controller load

l

Improve cooling

l

Check fan in the controller

OH51

203

PTC monitoring
(display when
C0119 = 2 or 5)

Motor too hot due to
impermissible high currents or
frequent and too long
acceleration processes

Check drive dimensioning

No PTC connected

Connect PTC or switch off monitoring

OU

c

DC−bus overvoltage
(message or TRIP
configurable in
C0310)

Mains voltage is too high

Check supply voltage

OUE

a

22

Braking operation

l

Increase deceleration times

l

For operation with an external
brake resistor:
– Check dimensioning,

connection and supply cable of
the brake resistor

– Increase deceleration times

Earth leakage at motor end

Check motor supply cable and motor
for earth fault (disconnect motor
from the inverter)