Fuses and cable cross-sections according to ul, Fuses and cable cross−sections according to ul, Electrical installation – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual

Page 124

Advertising
background image

Electrical installation

Mains connection
Fuses and cable cross−sections according to UL

5

l

124

EDK82EV222 DE/EN/FR 13.0

Fuses and cable cross−sections according to UL

Supply conditions

Range

Description

Fuses

l

Only in accordance with UL 248

l

System short−circuit current up to 5000 A

rms

: All classes are permissible

l

System short−circuit current up to 50000 A

rms

: Only classes "CC", "J", "T" or "R" permissible

Circuit−breaker

l

Only in accordance with UL 489

l

Manufacturer/type
– ABB: S 200 U Charact. K
– Schneider Electric: Multi9 C60 Charact. C
– Moeller: FAZ−C Charact. C

J Warnings!
Circuit breakers for 400/500 V devices only for use in WYE 480/277V source.

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!

Operation with increased rated power
Operation at an increased rated power is not UL−certified.

Operation at rated power

8200 vector

Rated fuse current / cable cross−section

Fuse

Circuit−breaker

Type

L1, L2, L3, N, PE

Type

L1, L2, L3, N, PE

Type

[A]

[AWG]

[A]

[AWG]

Mains 1/N/PE AC 230/240 V − operation without mains choke/mains filter

E82xV251K2C

10

16

15

14 4)

E82xV371K2C

10

16

15

14 4)

E82xV551K2C

10

16

15

14 4)

E82xV751K2C

15

14

15

14 4)

E82xV152K2C

20

2 x 16

25

2 x 14 4)

E82xV222K2C

20

2 x 16

30

2 x 14 4)

Advertising