Electrical installation

Mains connection

Fuses and cable cross−sections according to UL

5

l

125

EDK82EV222 DE/EN/FR 13.0

Rated fuse current / cable cross−section

8200 vector

Circuit−breaker

Fuse

8200 vector

L1, L2, L3, N, PE

Type

L1, L2, L3, N, PE

Type

[AWG]

[A]

[AWG]

[A]

Type

Mains 1/N/PE AC 230/240 V − operation with mains choke/mains filter

E82xV251K2C

10

16

15

14 4)

E82xV371K2C

10

16

15

14 4)

E82xV551K2C

10

16

15

14 4)

E82xV751K2C

15

14

15

14 4)

E82xV152K2C

20

2 x 16

25

2 x 14 4)

E82xV222K2C

20

2 x 16

30

2 x 14 4)

Mains 3/PE AC 230/240 V − operation without mains choke/mains filter

E82xV551K2C

6

18

15

14 4)

E82xV751K2C

10

16

15

14 4)

E82xV152K2C

15

14

15

14 4)

E82xV222K2C

15

2 x 16

20

2 x 14 4)

Mains 3/PE AC 230/240 V − operation with mains choke/mains filter

E82xV551K2C

6

18

15

14 4)

E82xV751K2C

10

16

15

14 4)

E82xV152K2C

15

14

15

14 4)

E82xV222K2C

15

2 x 16

20

2 x 14 4)

Mains 3/PE AC 400/500 V − operation without mains choke/mains filter

E82xV551K4C

6

18

15

14 4)

E82xV751K4C

6

18

15

14 4)

E82xV152K4C

10

16

15

14 4)

E82xV222K4C

10

16

15

14 4)

Mains 3/PE AC 400/500 V − operation with mains choke/mains filter

E82xV551K4C

6

18

15

14 4)

E82xV751K4C

6

18

15

14 4)

E82xV152K4C

10

16

15

14 4)

E82xV222K4C

10

16

15

14 4)

4)

Pin−end connector required