Commissioning

Parameter setting with the XT EMZ9371BC keypad

Vector control

7

l

143

EDK82EV222 DE/EN/FR 13.0

Comment

Switch−on sequence

14.

Start the motor parameter identification (C0148)

Only when the motor is cold!

A

Ensure that the controller is inhibited

Terminal X3/28 = LOW

B

Set C0148 = 1

Press

TV

C

Enable the controller

l

Terminal X3/28 = HIGH

l

The identification starts:
– Segment

c is off

– The motor consumes current and makes a

high−pitched" tone.

– The motor does not rotate!

D

If segment

c becomes active again after approx. 30 s,

inhibit controller again.

l

Terminal X3/28 = LOW

l

Identification is completed.

l

Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)

l

Measured and stored:
– Motor stator resistance (C0084) = Total

resistance of motor cable and motor

15.

Activate the motor temperature monitoring (C0119) if you
have connected a PTC or thermal contact to terminal X2.2
Lenze setting: switched off

Possible settings

(

152)

When all settings are complete:

16.

Select setpoint

E.g. via potentiometer at terminals 7, 8, 9

17.

Enable the controller

Terminal X3/28 = HIGH

18.

The drive is now running.

If the drive does not start, additionally press

u