Commissioning

Parameter setting with the XT EMZ9371BC keypad
Vector control

7

l

142

EDK82EV222 DE/EN/FR 13.0

Comment

Switch−on sequence

6.

Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for the
standard I/O)

7.

If required, adapt the fixed setpoints JOG.

A

JOG 1 (C0037)
Lenze setting: 20 Hz

Activation:
X3/E1 = HIGH, X3/E2 = LOW

B

JOG 2 (C0038)
Lenze setting: 30 Hz

Activation:
X3/E1 = LOW, X3/E2 = HIGH

C

JOG 3 (C0039)
Lenze setting: 40 Hz

Activation:
X3/E1 = HIGH, X3/E2 = HIGH

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

12.

Activate the operating mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)

13.

Enter the motor data

See motor nameplate

A

Rated motor speed (C0087)
Lenze setting: 1390 rpm

B

Rated motor current (C0088)
Lenze setting: depending on the controller

Enter the value for the motor circuit
configuration (star/delta) selected!

C

Rated motor frequency (C0089)
Lenze setting: 50 Hz

D

Rated motor voltage (C0090)
Lenze setting: depending on the controller

Enter the value for the motor circuit
configuration (star/delta) selected!

E

Motor cos

j (C0091)

Lenze setting: depending on the controller