Electrical installation

Mains connection
Connection plan for controllers type E82xVxxxK2C (230/240 V mains)

5

l

120

EDK82EV222 DE/EN/FR 13.0

Mains connection

Connection plan for controllers type E82xVxxxK2C (230/240 V mains)

(

Stop!

ƒ

Only connect the controller to the permitted mains voltage (

^ Technical data). A

higher mains voltage destroys the controller!

ƒ

Some controllers may only be actuated with a mains choke or mains filter. This
requirement can differ with regard to operation at rated power and operation at an
increased rated power.

ƒ

The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
fixed installation is required. The PE conductor has to be designed double.

E82EV551K2C

E82EV751K2C

X1.1

X1.1

E82EV251K2C

E82EV371K2C

E82EV152K2C

E82EV222K2C

X1.1

N

1.5 mm

2

1.5 mm

2

1.5 mm

2

1.5 mm

2

2.5 mm

2

2.5 mm

2

2.5 mm

2

2.5 mm

2

2.5 mm

2

2.5 mm

2

PE

L1

1/N/PE AC 230 V/240 V

+UG -UG

L1

L2/N L3/N

L1

PE

L2

PE

L1

2/PE AC 230 V/240 V

+UG -UG

L1

L2/N L3/N

L1

PE

PE

L1

L2

L3

3/PE AC 230 V/240 V

+UG -UG

L1

L2/N L3/N

L1

PE

PE

L1

L2

2/PE AC 230 V/240 V

+UG -UG

L1

L3 PE

L2/N

PE

L1

N

1/N/PE AC 230 V/240 V

+UG -UG

L1

L2/N

L3 PE

PE

L1

N

1/N/PE AC 230 V/240 V

L1

L2/N

PE

L2/N

PE

L1

L2

L3

3/PE AC 230 V/240 V

+UG -UG

L1

L3 PE

2/PE AC 230 V/240 V

PE

L1

L1

L2/N

PE

L2

0

0

8200vec012

0

Route two cables with 1.5 mm

2

each to the terminals!

X1.1/+UG, X1.1/−UG

Supply for DC−bus operation