Troubleshooting and fault elimination – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual

Page 160

Advertising
background image

Troubleshooting and fault elimination

Fault elimination
Fault messages

8

l

160

EDK82EV222 DE/EN/FR 13.0

Remedy

Cause

Fault

PC

1)

Keypad

LU

c

DC−bus
undervoltage

Mains voltage is too low

Check mains voltage

Voltage in DC−bus connection is
too low

Check power supply module

400 V controller is connected to
240 V mains

Connect controller to correct mains
voltage

OC1

a

11

Short circuit

Short circuit

l

Search for cause of short circuit;
check motor cable

l

Check brake resistor and cable to
brake resistor

Capacitive charging current of
the motor cable is too high

Use shorter/low−capacitance motor
cable

OC2

a

12

Earth fault

A motor phase has earth contact

Check motor; check motor cable

Capacitive charging current of
the motor cable is too high

Use shorter/low−capacitance motor
cable

Deactivate earth−fault detection for
test purposes

OC3

a

13

Controller overload
during acceleration
or short circuit

Set acceleration time is too short
(C0012)

l

Increase acceleration time

l

Check drive dimensioning

Defective motor cable

Check wiring

Interturn fault in the motor

Check motor

OC4

a

14

Controller overload
during deceleration

Set deceleration time is too short
(C0013)

l

Increase deceleration time

l

Check dimensioning of the
external brake resistor

OC5

a

15

Controller overload
during steady−state
operation

Frequent and too long overload
periods

Check drive dimensioning

OC6

a

16

Motor overload
(I

2

x t overload)

Motor is thermally overloaded by
e.g.

l

impermissible continuous
current

l

Check drive dimensioning

l

frequent or too long
acceleration processes

l

Check setting of C0120