Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual
Page 130
![background image](/manuals/565981/130/background.png)
Extensions for automation
Modules
Mounting and dismounting function modules
l
130
EDK82EV222 DE/EN/FR 13.0
Mounting
8200vec601
1.
Disconnect the drive controller from mains and wait at least 3 minutes!
2.
Remove the FIF cover
0 from the FIF interface.
3.
Remove protective cap
1 of the function module 2 and plug function module onto the FIF
interface.
4.
Insert the plug connector
3 into the contact strip of the function module until it snaps in.
Additionally fit the retaining clip so that the module cannot be removed together with the terminal
strips
5 during wiring:
5.
Insert the retaining clip
4 into the recess, place it on the function module and latch it.
6.
Wire the function module (see mounting instructions of the function module).
)
Note!
Keep the FIF cover
0 and the protection cover of the function module 1 so that you can
attach them again after you have dismounted the function module.
The controller can only be commissioned if a function module or the FIF cover
0 is