Commissioning

Parameter setting with E82ZBC keypad

Vector control

7

l

137

EDK82EV222 DE/EN/FR 13.0

Vector control

The following instructions apply to controllers equipped with a standard−I/O function module and
a three−phase AC motor which has been selected according to a power−based assignment.

Switch−on sequence

Comment

1.

Connect keypad

2.

Ensure that controller inhibit is active after mains
connection

Terminal X3/28 = LOW

3.

Switch on the mains

4.
5.

The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)

The USEr menu is active

6.

Go to the ALL menu

7.

Change to the

f mode to configure the basic settings for

your drive

Blinking on the display: 0050

8.

Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation

9.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

10.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

11.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

12.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

13.

Activate the operating mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)

14.

Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for
the standard I/O)