Commissioning

Parameter setting with the XT EMZ9371BC keypad

Vector control

7

l

141

EDK82EV222 DE/EN/FR 13.0

Comment

Switch−on sequence

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

12.

Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz

13.

Set the V

min

boost (C0016)

Lenze setting: depends on the controller type

The Lenze setting is suitable for all common
applications

14.

Activate the motor temperature monitoring (C0119) if you
have connected a PTC or thermal contact to terminal X2.2
Lenze setting: switched off

Possible settings

(

152)

When all settings are complete:

15.

Select setpoint

E.g. via potentiometer at terminals 7, 8, 9

16.

Enable the controller

Terminal X3/28 = HIGH

17.

The drive is now running.

If the drive does not start, additionally press

u

Vector control

The following instructions apply to controllers equipped with a standard−I/O function module and
a three−phase AC motor which has been selected according to a power−based assignment.

Switch−on sequence

Comment

1.

Plug in the keypad

2.

Ensure that controller inhibit is active after mains
connection

Terminal X3/28 = LOW

3.

Switch on the mains

4.

After approx. 3 s the keypad is in the operating level and
displays the output frequency (C0050) and the device
utilisation (C0056)

5.

For quick commissioning you select the "Quick start"
menu

The submenu "VectorCtrl qu" contains the codes
which you require for commissioning a standard
application. The digital inputs are configured in
Lenze setting:
X3/E1, X3/E2: activation of fixed setpoints (JOG)
X3/E3: activation of DC injection brake (DCB)
X3/E4: CW rotation/CCW rotation

A

Change the menu level with

V

B

Change to the "Quick start" menu and there to the
"VectorCtrl qu" submenu with

z z Z z

C

Change to the code level with

Z to parameterise your

drive