Mechanical installation
Mounting with thermal separation (push−through technique)
l
109
EDK82EV222 DE/EN/FR 13.0
Cutout in the control cabinet
Dimensions [mm]
8200 vector
a
1
b
1
Frame
E82DV152K2C
61
221
E82ZJ00x
E82DV222K2C
E82DV152K4C
E82DV222k4C
Mounting
1.
1.
2.
3.
3.
4.
5.
E82DV_002
1.
Slide on frame.
2.
Insert seal.
3.
Slide earthing clamps on the frame with the correct sides:
– The contact springs have to point towards the rear panel of the control cabinet.
– The cutouts of the seal specify the positions.
4.
Insert 8200 vector into cutout.
5.
Tighten by means of 8 screws M4x10.
– Tightening torque: 1.7 Nm (15 lb−in)
Advertising