Electrical installation
Mains connection
Connection plan for controllers type E82xVxxxK4C (400/500 V mains)
l
121
EDK82EV222 DE/EN/FR 13.0
Connection plan for controllers type E82xVxxxK4C (400/500 V mains)
(
Stop!
ƒ
Only connect the controller to the permitted mains voltage (
^ Technical data). A
higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter. This
requirement can differ with regard to operation at rated power and operation at an
increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
fixed installation is required. The PE conductor has to be designed double.
E82EV551K4C
E82EV751K4C
E82EV152K4C
E82EV222K4C
X1.1
X1.1
L2
PE
L1
L2
L3
3/PE AC 400 V
+UG -UG
L1
L3 PE
8200vec011
X1.1/+UG, X1.1/−UG
Supply for DC−bus operation