Electrical installation

Mains connection

Connection plan for controllers type E82xVxxxK4C (400/500 V mains)

5

l

121

EDK82EV222 DE/EN/FR 13.0

Connection plan for controllers type E82xVxxxK4C (400/500 V mains)

(

Stop!

ƒ

Only connect the controller to the permitted mains voltage (

^ Technical data). A

higher mains voltage destroys the controller!

ƒ

Some controllers may only be actuated with a mains choke or mains filter. This
requirement can differ with regard to operation at rated power and operation at an
increased rated power.

ƒ

The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
fixed installation is required. The PE conductor has to be designed double.

E82EV551K4C

E82EV751K4C

E82EV152K4C

E82EV222K4C

X1.1

X1.1

L2

PE

L1

L2

L3

3/PE AC 400 V

+UG -UG

L1

L3 PE

8200vec011

X1.1/+UG, X1.1/−UG

Supply for DC−bus operation