Commissioning – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual

Page 152

Advertising
background image

Commissioning

Important codes for quick commissioning

7

l

152

EDK82EV222 DE/EN/FR 13.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0034
*

v

(A)

uSEr

Range of
setpoint
selection
Application I/O

Observe jumper position of the
function module!

1

X3/1U, X3/1I

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V

2

X3/2U, X3/2I

1

Bipolar voltage −10 V ... +10 V

Minimum output frequency (C0010)
not effective

2

Current 0 ... 20 mA

3

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

4

Current 4 ... 20 mA open−circuit monitored

Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA

C0037

JOG1

20.00

−650.00

{0.02 Hz}

650.00

JOG = fixed setpoint
Additional fixed setpoints

ðC0440

C0038

JOG2

30.00

−650.00

{0.02 Hz}

650.00

C0039

JOG3

40.00

−650.00

{0.02 Hz}

650.00

C0050
*

uSEr

Output
frequency
(MCTRL1−NOUT)

−650.00

{Hz}

650.00

Read only: Output frequency without
slip compensation

C0087

Rated motor
speed

à

300

{1 rpm}

16000

à

Device−dependent

C0088

Rated motor
current

à

0.0

0.1 (A)

650.0

à

Device−dependent

0.0 ... 2.0 x rated output current of
the controller

C0089

Rated motor
frequency

50

10

{1 Hz}

960

C0090

Rated motor
voltage

à

50

{1 V}

500

à

230 V for 230 V controllers,
400 V for 400 V controllers

C0091

Motor cos

а

0.40

{0.1}

1.0

а

Device−dependent

C0119

v

Configuration
of motor
temperature
monitoring (PTC
input) / earth
fault detection

0

0

PTC input inactive

Earth fault
detection active

l

Configure signal output in C0415

l

If several parameter sets are
used, monitoring has to be set
separately for every parameter
set.

l

Deactivate earth fault detection
if the earth fault detection is
actuated unintentionally.

l

If the earth fault detection is
activated, the motor starts with a
delay of approx. 40 ms after
controller enable has been set.

1

PTC input active,
TRIP effected

2

PTC input active,
warning effected

3

PTC input inactive

Earth fault
detection inactive

4

PTC input active,
TRIP effected

5

PTC input active,
warning effected